FANG Chunhua, PAN Hong, LIU Yang, et al. Study on the Influence Regularity of High-speed Railway Harmonics on the 220 k V Side of Traction Transformer[J]. High voltageapparatus, 2018, 54(2): 140-146.
FANG Chunhua, PAN Hong, LIU Yang, et al. Study on the Influence Regularity of High-speed Railway Harmonics on the 220 k V Side of Traction Transformer[J]. High voltageapparatus, 2018, 54(2): 140-146. DOI: 10.13296/j.1001-1609.hva.2018.02.023.
Study on the Influence Regularity of High-speed Railway Harmonics on the 220 k V Side of Traction Transformer
通过仿真计算总结了高铁谐波对牵引变压器220 k V侧的影响规律。当高铁谐波传递至220 k V侧后
各次谐波有效值有不同幅度降低;谐波含有率也有不同的变化
3、5次谐波电流含有率均有增加
7
5
0次奇次谐波电流含有率均有所降低。当T线谐波电流相位与F线谐波电流相位的差值不同时
对220 k V侧影响也不同
当相位差在10°
5
0°内增加时
220 k V侧3、5、7次谐波电流含有率和总谐波畸变率均降低
当相位差在50°
9
0°内增加时
220 k V侧3、5、7次谐波电流含有率和总谐波畸变率均上升。算例结果表明
该研究方法简便明了
且计算误差在允许范围内
对高铁谐波治理有着重要参考意义。
Abstract
Special operation mode of high-speed railway will produce a large number of harmonics
and the harmon-ic will be traversed by the traction transformer into the main network 220 k V side
the main effect of the major net-work is worthy to make further studies and tests. Based on the harmonic data of the traction substation
the harmonicsource model based on the measured data is established. The influence of the high-speed railway harmonic on the220 k V side of the traction transformer is summarized by simulation. In this paper
based on the harmonic data m
ea-sured at traction substation
the harmonic source model is established. According to a lot of simulated results
the in-fluences of high-speed railway harmonics on 220 k V side of traction transformer are presented. When high-speed rail-way harmonics are transmitted to the 220 k V side
the effective value of each harmonic has different amplitude reduc-tion;and there are different changes in harmonic content
the third and fifth harmonic currents have increased
andthe 7
5
0 times odd harmonic current is reduced. When the difference between the phase of the T line harmonic cur-rent and the phase of the F line harmonic current is different
the effects on the 220 k V side are also different
andthe phase difference increased in the range of 10 degrees to 50 degrees
at the 220 k V side
the third
fifth and sev-enth the harmonic current content and total harmonic distortion rate are reduced
When the phase difference is in-creased from 50 degrees to 90 degrees
the third
fifth and seventh the harmonic current content and total harmonic dis-tortion rate of the 220 k V side increased. The results show that the method is simple and clear
and the calculation erroris within the allowable range
which has important reference significance for the high-speed railway harmonic control.