PENG Qingjun, JIANG Xiongwei, MA Yi, et al. Analysis of 35 k V Dry-type Air-core Reactors Turn-to-turn Field Distribution Based on the Finite Element Method[J]. High voltageapparatus, 2018, 54(2): 147-152.
PENG Qingjun, JIANG Xiongwei, MA Yi, et al. Analysis of 35 k V Dry-type Air-core Reactors Turn-to-turn Field Distribution Based on the Finite Element Method[J]. High voltageapparatus, 2018, 54(2): 147-152. DOI: 10.13296/j.1001-1609.hva.2018.02.024.
Analysis of 35 k V Dry-type Air-core Reactors Turn-to-turn Field Distribution Based on the Finite Element Method
对35 k V干式空心电抗器匝间放电故障分析和提高35 k V干式空心电抗器的可靠运行具有重要意义。为此
文中基于有限元仿真计算开展了35 k V干式空心电抗器匝间电场分布研究。研究结果表明:35 k V干式空心电抗器外层支路匝间电场强度大于内层支路的匝间电场强度
且由于35 k V干式空心电抗器电磁场分布的特殊性导致了每层支路中端部的匝间电场强度小于中间部分的匝间电场强度;10 k Hz下的匝间电压比与50 Hz下的匝间电压比近似相同。
Abstract
To study the turn-to-turn electric field distribution in 35 k V dry-type air-core reactor
has a greatsignificance on the mechanism of turn-to-turn discharge fault
and improve its reliability. Therefore
this papercarried out the research of turn-to-turn field distribution in dry-type air-core reactor based on the finite elementsimulations. The analysis results indicated that the intensity of inter-turn electric field in the outer branch is greaterthan that in the inner branch. The particularity of the electromagnetic field distribution in 35 k V dry-type air-corereactor leads to the result of end inter-turn electric field intensity in each layer of branch is less than that in themiddle section. The inter-turn voltage ratio under 10 k Hz and 50 Hz is approximately the same.