Research and Improvement on Mechanical Characteristics of 220 kV GIS Disconnector
based on a fault analysis of 220 kV GIS disconnector and the test data of other similar equipment
the mechanical characteristics of this type of GIS disconnector are studied in depth. It is proposed that the mechanical characteristic of the spring mechanism used for GIS disconnector is not stable
and should be replaced as anmotor-driving mechanism. At the same time
it is proposed that when the mechanical characteristics of the GIS isolating switch and the field mechanical characteristics test are 66 kV or above
the pulse time of the tester should be set to 120
2
00 ms
so as to ensure that the test instrument is consistent with the time of switching closing pulse in the background
therefore
the correctness of the electrical wi
ring in mechanism box is checked in an all-round way. This is a good method for checking if the disconnector switching closing in the right position.