TAN Dongxian, HE Yiling, LIN Jun, et al. Investigations on Insulation Characteristics of 12 kV Composite Insulated Switchgear[J]. High voltageapparatus, 2018, 54(4): 28-33+42.
TAN Dongxian, HE Yiling, LIN Jun, et al. Investigations on Insulation Characteristics of 12 kV Composite Insulated Switchgear[J]. High voltageapparatus, 2018, 54(4): 28-33+42. DOI: 10.13296/j.1001-1609.hva.2018.04.005.
Investigations on Insulation Characteristics of 12 kV Composite Insulated Switchgear
Applying composite insualtion to replace pure air insulation in the design of compact air-insulated metalenclosed switchgears for achieving the goal of compact design.More types of dielectrics and insulation interfaces coex-ist in composite insulation switchgears.This complex insulation configuration results in enormous difficult for calcu-lating the electric field distribution and evaluating insualtion performance.In this paper
a systemic investigation wasimplemented on composite insulation of contact arm
simulation and tests were completed under different insulationconfiguration and materials
results show that the maximum electrical field can not be used as the criteria to evaluat-ing whether breakdown occurs in composite insulation system
the electric field value in key location(samll gap andinterface)of composite insulation configuration possess decisive significance for evaluating the insulation withstandcapability.These results concluded in this papers can provide some significant proposals for the design of compositeinsulation configurations and simulations.