Diagnosis Study About Gas Leakage of GIS Chamber Based on Skewness and Kurtosis Indexes
Aiming at the shortcomings of traditional calculation standard of the SF
6
annual leakage rate which over-looked distribution trends
this paper presents a new calculation method—skewness and kurtosis calculation stan-dard. First
determining gas chamber pressure curve type and judging whether the gas pressure is abnormal
identify-ing whether the gas pressure is internal mutual leakage or external leakage by comparing the skewness and kurtosisindexes of two adjacent gas chamber pressures. Criterion based on skewness and kurtosis standard which can judgethe mutual internal leakage or external leakage is provided
and the criterion thresholds judging the mutual internalleakage
and external leakage are indicated by statistical deviation of the normal distribution of the sample data. Final-ly
the tests of numerical example and SF
6
gas chamber pressure data from the field have proved the effectiveness ofthe proposed criterion
compared with traditional calculation standard of the annual leakage rate
this criterion ismore accurate
and is able to distinguish between internal leakage and external leakage.