YUAN Huqiang, CHENG Jiandeng, LIU Wenze, et al. Diagnosis Method of HVDC MRTB Parallel Oscillating Device Fault Based on the Current Analysis[J]. High voltageapparatus, 2018, 54(4): 81-86.
YUAN Huqiang, CHENG Jiandeng, LIU Wenze, et al. Diagnosis Method of HVDC MRTB Parallel Oscillating Device Fault Based on the Current Analysis[J]. High voltageapparatus, 2018, 54(4): 81-86. DOI: 10.13296/j.1001-1609.hva.2018.04.012.
Diagnosis Method of HVDC MRTB Parallel Oscillating Device Fault Based on the Current Analysis
In order to confirm that the parallel oscillating device in metallic return transfer breaker(MRTB)is nor-mal or not
when the connecting mode of UHVDC system is changing from metallic return to earth return
this paperproposed an online MRTB parallel oscillating device diagnosis method based on current analysis. First
this paperdesigns a way to calculate the current of MRTB parallel oscillating device by delineating the closed surfaces and ap-plying the KCL law equation in those closed surfaces. Then
according to the characteristic of the calculated currentof MRTB parallel oscillating device
it can be diagnosed that the default status of the parallel oscillating device. Thecorrectness and effectiveness of this method proposed in this paper have been proved through the success and failureconversion cases of ±800 kV Chu-Sui UHVDC pole Ⅱ system.