LIU Shitao, WU Bo, WU Xutao, et al. Study on Guano Flashover Characteristics of Composite Insulators for 330 kV Transmission Line[J]. High voltageapparatus, 2018, 54(4): 135-141.
LIU Shitao, WU Bo, WU Xutao, et al. Study on Guano Flashover Characteristics of Composite Insulators for 330 kV Transmission Line[J]. High voltageapparatus, 2018, 54(4): 135-141. DOI: 10.13296/j.1001-1609.hva.2018.04.020.
Study on Guano Flashover Characteristics of Composite Insulators for 330 kV Transmission Line
330 kV line in Ningxia has repeatedly occurred bird fault tripping
a serious threat to the safeand stable operation of Ningxia power grid. There is still a lack of research about the guano flashover mechanism of 330 kV line and its factors at home and abroad. This paper firstly studied the hydrophobic property of contaminatedsilicone rubber in low temperature environment pollution. Then based on the relationship between the maximum con-tinuous length and guano parameters during the drop of guano
this paper studied the influence of drop way
dropchannel
conductivity
viscosity
volume
drop position and relative humidity on the flashover characteristic of 330 kV composite insulators in contaminated laboratory. The test results showed that the flashover probability of 330 kV com-posite insulator increases with the decrease of distance and the increase of guano. The flashover probability of guanoescaped from cross arm is lower than not escaped
and the insulators have higher flashover probability when with coro-na ring than that without corona ring. When the guano volume
conductivity
and the air relative humidity are large
the probability of occurrence of flashover is greater.
Influence of Contamination on Voltage Monitoring Board for Light Triggered Thyristor Converter Valve and the Corresponding Countermeasures
Simulation and Experimental Study on Partial Discharge Decomposition Components of Air-insulated Switchgear Cabinet Considering the Influence of Temperature and Humidity
Infrared Analysis of Nonlinear Heating Characteristics of Deteriorated Porcelain Insulator of 500 kV Transmission Lines
Further Discussion on Monitoring and Threshold of Moisture in SF6 Gas
Cleaning Data Analysis of 110 kV Substation Insulators
Related Author
XU Yongsheng
ZHANG Fuzeng
LIU Zichen
WANG Liming
YIN Fanghui
JI Hongquan
XIN Feng
LIU Ruoxi
Related Institution
Electric Power Research Institute, China Southern Power Grid
Shenzhen International Graduate School, Tsinghua University
State Grid Nanjing Power Supply Company
State Grid Beijing Electric Power Company Urban Power Supply Company