DUAN Jundong, XIE Yunhui, ZHANG Xiaofang. Effect of Current Measurement Value in Excitation Controller on Low Frequency Oscillation of Power System[J]. High voltageapparatus, 2018, 54(4): 170-176.
DUAN Jundong, XIE Yunhui, ZHANG Xiaofang. Effect of Current Measurement Value in Excitation Controller on Low Frequency Oscillation of Power System[J]. High voltageapparatus, 2018, 54(4): 170-176. DOI: 10.13296/j.1001-1609.hva.2018.04.025.
Effect of Current Measurement Value in Excitation Controller on Low Frequency Oscillation of Power System
The frequent occurrence of low frequency oscillation seriously affects the safe and stable operation of pow-er system. By analyzing the cause of the aggravation of the low frequency oscillation of power system
it is found thatthe current measurement value of adjustment unit of the generator excitation regulator may be one of the reasons forintensifying the low frequency oscillation. This paper for the generator excitation adjustment regulator difference vari-ation characteristic of unit current measurements are analyzed
using the Thevenin’s equivalent circuit analysismethod that current measurement and power angle of generator has the same amplitude oscillation characteristics
and its introduction influenced greater than that of the voltage measurement value on the low frequency oscillation.The simulation results based on MATLAB show that the low frequency oscillation is increased to a certain extent dueto the effect of the adjustment unit current measured value on the excitation system of the generator.