GAO Zhuqing, CAO Xiaobin, DU Junle, et al. Study on the Effect of Vertical Rod on Reducing Tower’s Impulse Grounding Resistance[J]. High voltageapparatus, 2018, 54(4): 182-187.
GAO Zhuqing, CAO Xiaobin, DU Junle, et al. Study on the Effect of Vertical Rod on Reducing Tower’s Impulse Grounding Resistance[J]. High voltageapparatus, 2018, 54(4): 182-187. DOI: 10.13296/j.1001-1609.hva.2018.04.027.
Study on the Effect of Vertical Rod on Reducing Tower’s Impulse Grounding Resistance
the main cause of lightning trip-out is large impulse resistanceof the tower grounding device. In view of how to use the vertical rod to reduce the impulse grounding resistance of tow-er
this paper establishes simulation model of typical tower grounding device to study the influence scope of differentlength vertical rod
the number and length of vertical grounding electrodes influence on resistance reducing effect.Through the study found that the different length of the vertical rod affects different area-the influence scope of 10 me-ter vertical rod is about 40 m
however
the influence scope of 3 m and 5 m vertical rod is about 5 m and 20 m respec-tively. When the total length of vertical grounding electrode under the same condition
the length of the vertical rod islonger
the resistance reduction effect is the better. With the increase in the number of vertical grounding electrodes
the resistance-reducing ratio is always saturated. This paper recommended that adding as much as possible long verti-cal rod at the place which the leakage current is weak
then according to the vertical rod’s impact area to increasethe right number of vertical rod. This conclusion can provide technical reference for the design and reconstruction ofthe tower grounding device.