DU Xin. Analysis and Treatment of Abnormal Partial Discharge Data in a 500 kV GIS Circuit Breaker[J]. High voltageapparatus, 2018, 54(4): 216-220+226. DOI: 10.13296/j.1001-1609.hva.2018.04.033.
Analysis and Treatment of Abnormal Partial Discharge Data in a 500 kV GIS Circuit Breaker
Partial discharge test is a very effective method of state monitoring method for gas insulated metal en-closed switchgear(GIS)
in the standard
the partial discharge detection must be carried out during the process ofGIS overhaul. This paper introduces the partial discharge data of a 500 kV GIS circuit breaker abnormal events foundin AC voltage test process
the final examination showed interrupter insulating support tube bottom fastening boltloosening caused by metal powder
carries on the inspection
and puts forward some suggestions to perfect the equip-ment maintenance project. This provides a good reference for the maintenance and test of the same kind of equipment.