Study on the Capacitive Voltage Rising of AC Test for Tank Type MOA in GIS
In order to check the performance of tank type metal oxide arrester(MOA)which is located into the GIS
the technical parameters of tank MOA should be detected. Because the tank type MOA is located into the GIS
thetest voltage could be acquired through the exterior bushing or induced voltage of PT. However
the ground capaci-tance of the testing circuit and the leakage reactance of testing transformer or PT would lead to the capacitance-raisedvoltage
which could make the tested equipment suffer higher voltage than applied voltage. In this paper
the reasonsof capacitance-raised voltage of the tank MOA in GIS are analyzed based on the test circuit. It is indicated that howthe ground capacitance and leakage inductance influence the capacitance-raised voltage. Some suggestions are pro-posed
to guide the hand-over test of tank type MOA in GIS.