LI Jianbo, GAO Wensheng, LIU Weidong. Evolution Process and Severity Assessment of the Partial Discharge Caused by Immobilized Metal Particles on DC GIL Insulator Surface[J]. High voltageapparatus, 2018, 54(5): 9-16.
LI Jianbo, GAO Wensheng, LIU Weidong. Evolution Process and Severity Assessment of the Partial Discharge Caused by Immobilized Metal Particles on DC GIL Insulator Surface[J]. High voltageapparatus, 2018, 54(5): 9-16. DOI: 10.13296/j.1001-1609.hva.2018.05.002.
Evolution Process and Severity Assessment of the Partial Discharge Caused by Immobilized Metal Particles on DC GIL Insulator Surface
Immobilized metal particles on DC GIL insulator surface significantly reduce the flashover voltage on theinsulator surface
which is a common defect in DC GIL. To study the evolution process and severity assessment ofpartial discharge caused by immobilized metal particles on DC GIL insulator surface
we established a 220 kV GIL equipment platform. By gradually increasing voltage and then using the ultraviolet viewer observed the entire partialdischarge evolution process on insulator surface. Meanwhile
analyzed the average amplitude and time interval ofpartial discharge. The results show that:the severity of partial discharge caused by the immobilized metal particles inthe insulator surface of the GIL can be classed into three levels: mild discharge
moderate discharge and severedischarge;as the discharge process intensified
the average amplitude and time interval of partial discharge followedthe change. The statistical parameter Sk/Kuof average amplitude and time interval of partial discharge can be used toevaluate the severity of the defect caused by immobilized metal particles on DC GIL insulator surface.
Research on Application of Microphone-optimized Spiral Arrays-based Acoustic Imaging Devices in Partial Discharge Localization
Study on Fiber Interferometric Partial Discharge Ultrasonic Sensing Method Based on Acoustic-optic Modulation and RF Phase Detection
High-frequency Sensing Technology of Partial Discharge of Switchgear Cabinet for Wind Solar & Energy Storage Stations in Gobi Deserts
Research on Influence of Piezoelectric Material Properties and Element Size on Sensitivity of Piezoelectric Sensor for Partial Discharge Monitoring of Transformer
Influence of Environmental Factors on Insulation Performance of Separable Connector for 12 kV Gas Filling Switchgear Cabinet
Related Author
YUE Song
GAO Fei
HAN Shuai
DONG Haoyuan
LI Jun
LI Xin
LIU Chao
QIAO Hui
Related Institution
Electric Power Research Institute of State Grid Tibet Company
China Electric Power Research Institute Co., Ltd.
Iflytek Co., Ltd.
Electric Power Research Institute, State Grid Hebei Electric Power Co., Ltd.
State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, North China Electric Power University