SONG Dongbo, HUANG Jie, ZHU Taiyun, et al. Localization and Analysis of a Partial Discharge Defects in GIS Solid Insulation[J]. High voltageapparatus, 2018, 54(5): 74-79+86.
SONG Dongbo, HUANG Jie, ZHU Taiyun, et al. Localization and Analysis of a Partial Discharge Defects in GIS Solid Insulation[J]. High voltageapparatus, 2018, 54(5): 74-79+86. DOI: 10.13296/j.1001-1609.hva.2018.05.012.
Localization and Analysis of a Partial Discharge Defects in GIS Solid Insulation
With the advancement of condition-based maintenance of electrical equipment
the live detection technol-ogy plays an increasingly important role in the state inspection of transmission and transformation equipment. Local-ization and analysis of a partial discharge(PD)defects in void of GIS solid insulation are introduced. First
the type ofdischarge is confirmed by UHF(ultra high frequency)PD detection method combined with the characteristics of PDspectrum. Then
the position of the defects is accurately located through channel signal reach time delay of the high-speed oscilloscope with consideration of the equipment structure. Finally
X-ray digital imaging detection and PDmeasurement are performed and find that there is a void inside the post insulator
and the PD is seriously exceeded
which proves the correctness of the location analysis. The characteristics of partial discharge with the change of volt-age are analyzed. In addition
the advantages and disadvantages of commonly used PD detection techniques are sum-marized and analyzed to provide reference for diagnosis and analysis of GIS insulation defects.