WU Shengbin, JIANG Xu, XIN Zhaozhao, et al. Simulation Analysis and Structure Optimization Based on the Hydrostatic Test of 252 kV Three-phase Basin-type Insulator[J]. High voltageapparatus, 2018, 54(5): 133-137+143.
WU Shengbin, JIANG Xu, XIN Zhaozhao, et al. Simulation Analysis and Structure Optimization Based on the Hydrostatic Test of 252 kV Three-phase Basin-type Insulator[J]. High voltageapparatus, 2018, 54(5): 133-137+143. DOI: 10.13296/j.1001-1609.hva.2018.05.021.
Simulation Analysis and Structure Optimization Based on the Hydrostatic Test of 252 kV Three-phase Basin-type Insulator
The destructive hydrostatic test of 252 kV three-phase basin-type insulator is described in this paper.Inorder to clarify why the destructive hydrostatic test of three-phase basin-type insulator could not meet the standardrequirements
investigations are carried out in this paper.Firstly
the three-phase basin-type insulator is modeled
simulated and analyzed.It is specified that the stress concentration at the intersection of three-phase basin-typeinsulators causes lower pressure during destructive hydrostatic test.Secondly
the structure of the insulator isoptimized and its ability of resisting compression is improved remarkably by changing the stress concentration from‘Y’type distribution to‘△’type distribution.Finally
some basic ideas for mechanical strength in optimizationdesign are proposed
which are that simulations should be taken into account during the mechanical strength designfor 252 kV three-phase basin-type insulator.Therefore
the work in this paper can provide useful references for thedesign of three-phase basin-type insulators.