Simulation Analysis on Transient Overvoltage of Asymmetric Short Circuit in Cable Collector Networks of Offshore Wind Farm
In order to research the high transient overvoltage amplitude which caused by asymmetrical short circuitin large-scale offshore wind farm cable network
this paper builds a 300 MW offshore wind farm transient calculationmodel using PSCAD/EMTDC electromagnetic transient simulation software. The influence of fault point
location oftransformer
number of single feeder fan and feeders on transient overvoltage and the overvoltage produced by failuresub-gate are emphatically studied. The simulation results show that transient overvoltage caused by single-phase short-circuit is greater than over-voltage caused by tripping after the fault
and the maximum amplitude can be up to 2.5 p.u..On this basis
this paper further studies overvoltage suppression measures owing to single-phase short-circuit fault
when the arrester and RC protector coordinately applied on the high-voltage side of motor-side transformer
overvolt-age can be suppressed to 2.24 p.u.
this will provide a certain reference for internal electrical system design of off-shore wind farm and insulation design of fan-side transformer.