HE Lizhu, WU Jingfeng, ZHANG Lu, et al. Researches on Ferromagnetic Resonance Calculation and Harmonic Elimination Measures in Substation Based on EMTP-ATP[J]. High voltageapparatus, 2018, 54(5): 210-216.
HE Lizhu, WU Jingfeng, ZHANG Lu, et al. Researches on Ferromagnetic Resonance Calculation and Harmonic Elimination Measures in Substation Based on EMTP-ATP[J]. High voltageapparatus, 2018, 54(5): 210-216. DOI: 10.13296/j.1001-1609.hva.2018.05.033.
Researches on Ferromagnetic Resonance Calculation and Harmonic Elimination Measures in Substation Based on EMTP-ATP
After the single-phase grounding fault occurs in the substation
the ferromagnetic resonance of the voltagetransformer(TV)is easily triggered
which causes the frequent fusing of the TV fuse and influences the safe operationof the power system. For researching the essential laws and influence factors of ferromagnetic resonance in substa-tion
based on the EMTP-ATP electromagnetic transient simulation software and considering the nonlinear character-istics of TV core
a distributed parameter model of ferromagnetic resonance calculation in a 35 kV substation is es-tablished. The cause of ferromagnetic resonance in substation is analyzed
and the restraining measures are put for-ward. The research shows that the single phase ground disappearance time determines whether TV will excite ferro-magnetic resonance. If the voltage of the non fault phase is instantaneous maximum
the most severe ferromagneticresonance of TV will occur. The arc suppression coil and the harmonic eliminator should be preferred in the substa-tion harmonic elimination measures
and the second is to put the damping resistor in the open triangular winding. Af-ter the arc suppression coil is put into operation
the TV three-phase current is reduced to far less than its rated cur-rent at the time of earth disappearance
which fundamentally avoids the fusing of TV fuse. 35 kV side adding arc sup-pression coil as no effect on suppressing 10 kV ferromagnetic resonance. When installing the harmonic eliminator
the TV three phase current should not exceed its rated value to avoid fuse while ensuring the suppression of ferromag-netic resonance. The smaller the input resistance value of TV open delta winding is
the better the inhibition effectfor ferromagnetic resonance. But the larger the three-phase current of TV is
the easier it will burn the fuse. The timeof the earth’s disappearance should be accurately judged
and the damping resistor can be switched accurately.