FENG Nanzhan, LI Qi, KONG Xu, et al. Measurement and Analysis of the VFTO Radiation Field of the Disconnector Operation in the 330 kV Switching Station[J]. High voltageapparatus, 2018, 54(5): 217-222.
FENG Nanzhan, LI Qi, KONG Xu, et al. Measurement and Analysis of the VFTO Radiation Field of the Disconnector Operation in the 330 kV Switching Station[J]. High voltageapparatus, 2018, 54(5): 217-222. DOI: 10.13296/j.1001-1609.hva.2018.05.034.
Measurement and Analysis of the VFTO Radiation Field of the Disconnector Operation in the 330 kV Switching Station
In order to study the waveform characteristics of the transient radiation field produced by the operation ofdisconnector
the radiated electric field generated by the operation of disconnector in the 330 kV Switching station ismeasured and analyzed. First
an electric field measurement system based on optical fiber is developed. Then veryfast transient overvoltage(VFTO)radiation field generated by operation of disconnector on the different side is mea-sured in the switch station. The measurement results are analyzed both in time domain and frequency domain. The re-sults show that amplitude of the electric field generated by the operation of disconnector at 3 m away from the discon-nector can reach 4.65 kV/m. The radiated electric field has a spectrum below 200 MHz
especially in some character-istic frequencies. The VFTO radiation field generated by the operation of disconnector on the busbar side and outgo-ing line side has different spectrum distribution. The VFTO radiation field generated by the opening and closing oper-ation of disconnector has different spectrum distribution.