Simulation Study on Pollution Accumulation Characteristics of XSP-160 Porcelain Three Umbrella Insulators
In order to study the contamination characteristics of porcelain three umbrella insulators and the influence of particle charge. Using COMSOL
a pollution accumulation modle of the wind tunnel at North China Electric Power University was built
and a simulation of the pollution accumulation characteristics of the XSP-160 porcelain three umbrella insulators was conducted
then
the simulation results were compared with the results from the wind tunnel test conducted at the campus. The verification results confirm the rationality of the simulation method. Based on these results
a simulation study was conducted on the natural contamination characteristics of the insulator to analyze the effects of individual factors and composite factors such as wind speed
particle size
particle charges
and voltage type on the natural pollution accumulation characteristics of insulators. The results show that DC voltage leads to a greater overall deposition of contaminants on the insulator surface and a faster rate of increase. However
the values of the deposition under AC voltage is slightly larger than that on the unelectrified state. Under DC condition
the greater the particle charge
the deposition is higher. The propportion of NSDDDCto NSDDACis 0.98
2.24 and 3.90
respectively
when the particles are uncharged
normal charged
and double charged
the propportion of NSDDDCto NSDDACapplroximately linearly increases with increasing particle chanrge.
Analysis of Coupled Structural Responses of Circuit and Equipment in Converter Substation Under Seismic Action
Simulation and Characteristic Analysis of Seismic Response of Coupling System of Flexible Conductors and Electrical Equipment in Substation
Numerical Simulation of Condensation and Influencing Factors Analysis of 10 kV High Voltage Switchgear
Research on Characteristics of Dielectric Barrier Discharge Load Under Pulse Excitation
Research and Mechanism Analysis of Electrically Induced Combustion Test Caused by Insulation Faults of Cable for Full-size High-voltage Switchgear Cabinet
Related Author
LI Guanghui
WANG Jinxiong
JIANG Weipeng
ZHANG Shihong
YANG Xu
LI Guanghui
LI Qiang
YU Jinyun
Related Institution
CSG Extra High Voltage Power Transmission Company, Dali Bureau
China Southern Power Grid Co., Ltd.
Electric Power Research Institute of EHV Power Transmission Company
Hubei Provincial Engineering Technology Research Center for Power Transmission Line, China Three Gorges University
College of Electrical Engineering & New Energy, China Three Gorges University