On-site Error Calibration Technology Under High Current for 1 000 kV Current Transformer
In error calibration test of 1 000 kV AC current transformer(CT)
the test current is as high as 7 200 A
so traditional test methods are no longer applicable. In this study
taking the test of 1 000 kV AC CT calibration in Beijingxi UHV Substation for example
a current-promoting method with high ratio is proposed
including impendence characteristic
reactive power compensation technique
and equipment parameters in the testing
and the data of the test circuit are analyzed. It is revealed that proper reactive power compensation for primary circuit is necessary to complete the error calibration test
and for the current transformer with shield on its inner wall
the maximum impact of the primary conductor’s eccentricity on the error data reaches 27%.