LI Guanjun, YAN Shengchi, CUI Hongfen, et al. Study on the Low Voltage Test Method Through Electric Closed Bench for Photovoltaic System[J]. High voltageapparatus, 2018, 54(6): 205-211.
LI Guanjun, YAN Shengchi, CUI Hongfen, et al. Study on the Low Voltage Test Method Through Electric Closed Bench for Photovoltaic System[J]. High voltageapparatus, 2018, 54(6): 205-211. DOI: 10.13296/j.1001-1609.hva.2018.06.031.
Study on the Low Voltage Test Method Through Electric Closed Bench for Photovoltaic System
Photovoltaic(PV)power generation system is required to pass the low-voltage-ride-through(LVRT)testbefore access to the power grid. Current LVRT test schemes are generally based on test bench applyingimpedance-based voltage divider which is costly and difficult to realize in the labs. In this paper
an electricclosed loop LVRT test scheme and its corresponding test bench for PV generation
based on fully-ratedconverter
is proposed. By applying three phase half-bridge topology and electric closed loop structure for DCbus
the power consumed by the inverter and the bench is decreased
which facilitates the bench to apply inthe labs. Several typical types of voltage sag are analyzed and specific implementation methods for the bench aregiven in the paper. Finally
comparative analysis is carried out between the proposed test bench and that basedon the impedance-based voltage divider through simulation
and the result verifies the effectiveness of theproposed LVRT test scheme.