LI Jiangtao, GU Yue, REN Ziyuan, et al. Analysis on the Turn-off Electrical Stress of High Voltage Power Thyristor Valve[J]. High voltageapparatus, 2018, 54(7): 206-210.
LI Jiangtao, GU Yue, REN Ziyuan, et al. Analysis on the Turn-off Electrical Stress of High Voltage Power Thyristor Valve[J]. High voltageapparatus, 2018, 54(7): 206-210. DOI: 10.13296/j.1001-1609.hva.2018.07.028.
Analysis on the Turn-off Electrical Stress of High Voltage Power Thyristor Valve
The voltage stress and current stress caused by turn-off process of high voltage power thyristor are two im-portant research focuses on its electric characteristics. The thyristor models in some programs
such as PSCAD/EMT-DC and MATLAB-Simulink
are ideal models
however the turn-off process influences the transient characteristicsof thyristor. Based on common-used exponential model of turn-off current
taking the thyristor 5 STP34 Q5200 for ex-ample
this paper introduces a practical simulation model in detail by utilizing MATLAB-Simulink. This thyristorturn-off model took the influence of the reverse recovery current and electric charges into consideration and is veri-fied in DC testing circuits in product manual. Furthermore
the interference to the turn-off electrical stress on high-voltage power thyristor caused by forward current
changing rate of current
and snubber circuit parameters are dis-cussed in detail. It is concluded that the simulation method is useful for the analysis of the turn-off electrical stress onthyristor.