Research of DC Leakage Current and DC Voltage Distribution on the AC Filter Porcelain Column Circuit Breakers Under Humid and Contamination Conditions
In order to simulate the DC voltage distribution after the ACF porcelain column circuit breaker breaking capacitive load
this paper studies the distribution characteristics of the double fracture voltage and the U-I characteristics of breaker under humid conditions in the artificial climate chamber. Moreover under the condition of different fracture surface contamination ratios and environmental humidity
the leakage current and the fracture surface of the DC voltage are measured by using the DC high voltage generator which can make the circuit breaker double fracture at the same time so as to withstand DC high voltage. The experimental results show that there are differences on the surface conductivity of the two fracture surfaces when the environmental relative humidity reached 90% and above. Therefore
the DC voltage on the load side is mostly concentrated in the same fracture surface after opening the capacitive load
and
the leakage current of the fracture surface tends to increase sharply as the relative humidity increases. Besides
the research direction of the DC voltage distribution is put forward in this paper.