Fast Remove System and Its DC Circuit Breaker for Flexible DC Transmission Fault
the flexible HVDC system cannot realize DC side short circuit fault clearing
it leads to chronic failure of all converters. To solve this problem and improve the reliability of the system
this paper researches the mechanism of fault current
the principle of DC interruption and simulates the influence of transfer parameters on DC breaking performance;proposes a mechanical DC circuit breaker of 500 A and a method of clearing the DC fault using the DC circuit breaker. Finally
building a low frequency oscillation circuit verifies the interruption performance of the breaker. The results show that the breaker stably breaks 500 A. The method can effectively shorten the system recovery time