WANG Shaohua, YAN Libing, LI Te, et al. Key Problems of Design for AC 500 kV Cross-linked Polyethylene Insulation Submarine Cable[J]. High voltageapparatus, 2018, 54(8): 225-230+236.
WANG Shaohua, YAN Libing, LI Te, et al. Key Problems of Design for AC 500 kV Cross-linked Polyethylene Insulation Submarine Cable[J]. High voltageapparatus, 2018, 54(8): 225-230+236. DOI: 10.13296/j.1001-1609.hva.2018.08.035.
Key Problems of Design for AC 500 kV Cross-linked Polyethylene Insulation Submarine Cable
In order to develop world’s first 500 kV cross-linked polyethylene insulation submarine cable
the critical technology during design are summarized such as the design of the AC resistance
the selection of insulation buffer layer and the electric field design of flexible joint. Owning to the distance among the different phases submarine cable conductors
the neighbor effect on the AC resistance could be neglected. The buffer layer could be selected by thermal expansion test of insulated cable conductor. The control of the electric field at the interface between the flexible joint and the cable is the key to design the electric field inner submarine cable flexible joint. Calculation of induced voltage on the cable metal sheath and armor layer is the important basis to confirm the position of the middle ground.