ZHU Qingcheng, LIU Zixun, LIU Wenxuan, et al. Arcing Duration and Erosion of CuW Contact Under DC Load and Different Surrounding Atmospheres[J]. High voltageapparatus, 2018, 54(9): 6-11.
ZHU Qingcheng, LIU Zixun, LIU Wenxuan, et al. Arcing Duration and Erosion of CuW Contact Under DC Load and Different Surrounding Atmospheres[J]. High voltageapparatus, 2018, 54(9): 6-11. DOI: 10.13296/j.1001-1609.hva.2018.09.002.
Arcing Duration and Erosion of CuW Contact Under DC Load and Different Surrounding Atmospheres
Surrounding atmospheres in hermetically sealed switching devices significantly affect their arc extinctionand electrical endurance. To better understand the effects of atmosphere on arcing duration and erosion of the con-tact
experiment was conducted with the CuW70 contact material under the DC supply voltage of 200
5
00V
the re-sistive load current of 40
1
50A
and the respective surrounding atmospheres of air
N
2
CO
2
and O
2
. It was found thatthe sequences of breaking arc duratiom for these atmospher
es changed with the supply voltage. O2 always had the lon-gest breaking arc duratiom
and N
2
showed shorter breaking arc duratiom than CO
2
in the case of 200
3
00V
but CO
2
showed shorter breaking arc duratiom than N
2
in the case of 400
5
00V. Experiment also indicated the anodes sufferedmass loss in all atmospheres