XU Zhengyu, LI Jinzhong, ZHANG Shuqi, et al. Analysis on Three Field Measurement Methods of Sound Power of UHV Power Transformer[J]. High voltageapparatus, 2018, 54(9): 129-134+141.
XU Zhengyu, LI Jinzhong, ZHANG Shuqi, et al. Analysis on Three Field Measurement Methods of Sound Power of UHV Power Transformer[J]. High voltageapparatus, 2018, 54(9): 129-134+141. DOI: 10.13296/j.1001-1609.hva.2018.09.020.
Analysis on Three Field Measurement Methods of Sound Power of UHV Power Transformer
The UHV power transformer is the main noise source in a UHV power substation. Accurate measurementof the transformer’s sound power is very important for noise control of power substation. In this study
the sound pres-sure based method
the discrete point sound intensity based method
and the scanning sound intensity based methodwere used to measure the sound power of a 1 000 kV UHV power transformer field. Results show that in the externalnoise interference and firewall reflecting sound environment
the latter two measurement methods based on sound in-tensity gain higher accuracy than the sound pressure based measurement method
indicating the two sound intensitybased methods are all suitable for in-site sound power measurement of audible noise from the 1 000 kV UHV powertransformer. In addition
the scanning sound intensity based method spent the shortest measurement time.