XIAO Caixia, LI Lin, JI Feng, et al. Calculation and Test of the Loss and Hot-point Temperature Rise of the UHV Dry-type Smoothing Reactor[J]. High voltageapparatus, 2018, 54(9): 177-182+190.
XIAO Caixia, LI Lin, JI Feng, et al. Calculation and Test of the Loss and Hot-point Temperature Rise of the UHV Dry-type Smoothing Reactor[J]. High voltageapparatus, 2018, 54(9): 177-182+190. DOI: 10.13296/j.1001-1609.hva.2018.09.028.
Calculation and Test of the Loss and Hot-point Temperature Rise of the UHV Dry-type Smoothing Reactor
To analyze the loss and temperature rise of the dry-type smoothing reactor in UHVDC transmission systemand obtain the hot-point location and hot-point temperature rise
we develop a calculation method of DC current lossand harmonic current loss distributions in each winding package of the smoothing reactor. Taking a ±800 kV/4 000 AUHV dry-type smoothing reactor for example
we analyze the difference of the loss distributions between the tempera-ture rise test condition under equivalent DC current and the operation condition containing harmonic current loss.We obtain the temperature rise distribution through temperature field calculation in the condition of temperature risetest
and verify the reliability of the simulation calculation results through corresponding temperature rise test. More-over
we compare the difference of the temperature rise distributions between the practical operation condition andthe temperature rise test condition
and the results show that the research of the hot-point temperature rise of asmoothing reactor only by the temperature rise test under equivalent DC current is not reasonable. It is necessary tofocus on the study of loading frequency-mixing current to improve the accuracy of the temperature rise test.