LU Wenhao, CHEN Bin, LIN Siyuan, et al. Anti-interference Research on Live Test of DC Arresters in Converter Station[J]. High voltageapparatus, 2018, 54(9): 191-196.
LU Wenhao, CHEN Bin, LIN Siyuan, et al. Anti-interference Research on Live Test of DC Arresters in Converter Station[J]. High voltageapparatus, 2018, 54(9): 191-196. DOI: 10.13296/j.1001-1609.hva.2018.09.030.
Anti-interference Research on Live Test of DC Arresters in Converter Station
The leakage current of DC arresters under CCOV is too low to catch
and it is easily to be interfered by ex-ternal conditions. There is seldom anti-interference research on live test of converter station DC arresters in domestic.This article tests the leakage current of DC arresters under CCOV in laboratory
and analyzes the influence of DCvoltage fluctuation
temperature and surface contamination on leakage current. The anti-interference measures are al-so proposed. The conclusions are as follow:(1)High amplitude DC voltage fluctuation will influence the live test re-sults of DC arresters. But within the range of ±3% that is permitted in DC system
the relationship between leakagecurrent and voltage fluctuation is linear. The temperature must be recorded in order to convert the leakage current;(2)Within the normal temperature range of arrester
the maximum variation of leakage current is less than 5 μA. Theleakage current is not affected by the internal temperature of the arrester;(3)The interference of surface contamina-tion on the leakage current test result is serious. In the condition of surface contamination on DC arresters
shieldring must be added when carrying out live test. The installation position can be selected at two to three umbrellas dis-tant from the flange in low voltage end of the arrester.