WEI Peng, ZHOU Qian, WANG Chenggen, et al. Study on the Method of Suppressing Power Oscillation with Braking Resistor in UHVAC/DC Coupling System During Commutation Failure[J]. High voltageapparatus, 2018, 54(10): 15-20+27.
WEI Peng, ZHOU Qian, WANG Chenggen, et al. Study on the Method of Suppressing Power Oscillation with Braking Resistor in UHVAC/DC Coupling System During Commutation Failure[J]. High voltageapparatus, 2018, 54(10): 15-20+27. DOI: 10.13296/j.1001-1609.hva.2018.10.003.
Study on the Method of Suppressing Power Oscillation with Braking Resistor in UHVAC/DC Coupling System During Commutation Failure
With the increasing coupling degree of UHVAC/DC system
how to suppress UHVAC link power oscilla-tion caused by UHVDC commutation failure is an urgent problem to be solved in AC/DC hybrid power grid control. Inthis paper
a method of suppressing power oscillation by commutating braking resistor on commutation side duringcommutation failure is proposed. In the RTDS Chang-Nan-Jing and Jingsu UHVAC equivalent power grid is built
ac-tual control and protection device are built to form a closed loop simulation platform with RTDS. Its performance re-mains highly consistent with actual UHVDC project in protection functions
behavior under fault of AC and DC andother aspects of characteristics. The effect of different braking resistances and different DC power on the power oscil-lation is simulated and analyzed
the braking resistor logic is verified. The results show that the control logic of brak-ing resistor proposed in this paper can effectively suppress the power oscillation on the tie line during the commuta-tion failure of the UHV AC/DC coupling system