GUO Xianshan, LIU Yanjie, FU Ying, et al. Analysis of Influence of Sliding Fittings on Seismic Performance of Interconnected High Voltage Electrical Equipment[J]. High voltageapparatus, 2018, 54(10): 221-226+233.
GUO Xianshan, LIU Yanjie, FU Ying, et al. Analysis of Influence of Sliding Fittings on Seismic Performance of Interconnected High Voltage Electrical Equipment[J]. High voltageapparatus, 2018, 54(10): 221-226+233. DOI: 10.13296/j.1001-1609.hva.2018.10.036.
Analysis of Influence of Sliding Fittings on Seismic Performance of Interconnected High Voltage Electrical Equipment
The structural system of electrical equipment connected with the hard tube can effectively solve the defor-mation caused by temperature variation
and also can reduce the dynamic coupling interaction between connecteddevices. Influence on the seismic performance of interconnected equipment is great by ways of sliding fittings
whichhas the characteristics of low cycle hysteresis and energy dissipation
or other connection mode to connect the hardtube. In this paper
we mainly researches on a high voltage DC field circuit system
the analysis method and the es-tablishment of the finite element model are briefly introduced
and the concrete steps of simulation analysis is put for-ward. By analyzing the stress
which is under seismic conditions of conventional seismic design
of the DC circuitsystem with different connection modes and checking the strength of the key parts
the influence of the connectionmodes on the dynamic characteristics and seismic performance of high voltage circuit system are comprehensivelystudied. Several useful conclusions are drawn
and the simulation results could provide reference for power engineer-ing and seismic strengthening design.