Research on Long-interval Sparse Partial Discharge in GIS and Its Sudden Breakdown
Partial discharge(PD)detection is applied to on-line live monitoring of gas insulated switchgear(GIS).However
false alarm and missing alarm often happen
particularly some sudden breakdown or flash-over occurredin GIS could not be detected in time. In this study
the shortcomings of current PD detection and diagnosis technolo-gies were analyzed
then an assumption was put forward that some sudden breakdown or flash-over of GIS might beinduced by accumulated long-interval sparse partial discharge
which was not detected by PD detection devices. Asurface defect PD model on GIS spacer was established in laboratory to demonstrate the existence of the long-intervalsparse partial discharge when long time and relatively low voltage was applied on the PD model. The statistic proper-ties of the time sequence of PD pulses and the phase resolved partial discharge(PRPD)spectrum were analyzed. Fur-ther
an on-site live detection of PD was performed for a real UHV GIS
and a doubtful cavity long-interval dischargewas detected. The time sequence features and PRPD spectrum of the discharge were comparatively studied. This study may facilitate effective detection and early warning of this kind of sudden breakdown or flash-over of GIS.