Multi-terminal PD Detection Technology of Transformer Based on Wide Bandwidth Pulse Current Method
To understand the information of partial discharge(PD)and the influence of transformer winding on PD signal propagation
two defect models of suspended discharge and point discharge are built in a 35 kV transformer.The signal at each detection point is measured based on the wide bandwidth pulse current method
and the character-istics of PD signals in different types and at different positions are analyzed. Result shows that: the signal waveformsof different defects are similar but their statistical characteristics are different;the signal from the bushing tap has amore significant change compared with the signals from the core and the neutral point of the winding when PD occurs in different phases;and the winding has a"frequency selection"effect for PD signal.