Field Application of Acoustic-electrical Combination Method in the PD Defect Location of Main Transformer
a field application case of the acoustic-electrical combination method in partial discharge(PD)detection and localization of No.1 transformer in a 110 kV substation in Chengdu is introduced. For the abnor-mal discharge signal found in the acceptance test
a rough location is first performed using the detection impedancemethod to determine the approximate range of the discharge source. Secondly
based on the different propagationcharacteristics of acoustic-electrical signals of PD
and combined with ultrasonic testing technology
an acoustic-electric combination method is used to perform secondary accurate localization of the discharge source. Finally
therepetitive measurement of the PD signal after the defect processing and finite element method are performed to verify the accuracy and effectiveness of the acoustic-electrical combination method in the PD location of the transformer.