DAN Shuheng, YU Xiaohan. Effect of Arc-gap Resistance on Transient Recovery Voltage of Generator Circuit Breaker[J]. High voltageapparatus, 2018, 54(12): 36-42.
DAN Shuheng, YU Xiaohan. Effect of Arc-gap Resistance on Transient Recovery Voltage of Generator Circuit Breaker[J]. High voltageapparatus, 2018, 54(12): 36-42. DOI: 10.13296/j.1001-1609.hva.2018.12.006.
Effect of Arc-gap Resistance on Transient Recovery Voltage of Generator Circuit Breaker
To reveal the effect of arc-gap resistance on transient recovery voltage of a generator circuit breaker during breaking process
the electromagnetic transient simulation software ATP-EMTP is employed to analyze the transient recovery voltage of the generator circuit breaker with different arc-gap resistance during breaking a three-phase short circuit fault
and obtain the relationship between the transient recovery voltage and the arc-gap resistance.Simulation shows that the rise rate of the transient recovery voltage positively relates to the climb rate of the arc-gap resistance
so the reduction of the climb rate of arc-gap resistance results in a decrease of the rise rate of transient recovery voltage;and in the breaking process
the generator circuit breaker with higher arc-gap resistance generates smaller peak value of the transient recovery voltage.