ZHANG Jun, WU Jinlong, WANG Xianwei, et al. Analysis of Impacting Factors on Breaking Capacity of Modular Hybrid DC Circuit Breaker[J]. High voltageapparatus, 2018, 54(12): 204-211.
ZHANG Jun, WU Jinlong, WANG Xianwei, et al. Analysis of Impacting Factors on Breaking Capacity of Modular Hybrid DC Circuit Breaker[J]. High voltageapparatus, 2018, 54(12): 204-211. DOI: 10.13296/j.1001-1609.hva.2018.12.031.
Analysis of Impacting Factors on Breaking Capacity of Modular Hybrid DC Circuit Breaker
Flexible high voltage direct curren(tHVDC)grid based on half-bridge sub-modules modular multi-level converter(HBSM-MMC)and DC circuit breaker is an effective approach to implement large-scale renewable energy integration and accommodation
it would be used widely in future.Flexible HVDC grid technology is mainly limited to the high voltage DC circuit breaker.It is necessary and significant to research the breaking process and capability impact factors of DC circuit breaker for flexible HVDC grid.Firstly
the operation of HBSM-MMC and modular hybrid DC circuit breaker are analyzed in this paper.Based on this
impact factors of modular hybrid DC circuit breaker breaking time would be analyzed comprehensively.Above this
the overvoltage impact factors of modular hybrid DC circuit breaker in flexible HVDC grid are calculated.Finally
modular hybrid DC circuit breaker and flexible HVDC grid model is built by PSCAD/EMTDC
the breaking capability impact factors is simulated.According to the analysis and result
breaking capacity would be upgraded by decreasing mechanical switch breaking time
decreasing capacitance of commutation branch and adjusting arrester voltage rating.