WANG Zan, FANG Yijun, MEI Nian, et al. Discussion on Selection of DC Grounding Point for Flexible DC Converter Station[J]. High voltageapparatus, 2018, 54(12): 212-217.
WANG Zan, FANG Yijun, MEI Nian, et al. Discussion on Selection of DC Grounding Point for Flexible DC Converter Station[J]. High voltageapparatus, 2018, 54(12): 212-217. DOI: 10.13296/j.1001-1609.hva.2018.12.032.
Discussion on Selection of DC Grounding Point for Flexible DC Converter Station
In order to protect people’s safety and protect the equipment from being destroyed
the possible operation way of a true bipolar flexible DC transmission project is analyzed in this paper.The grounding of system security operation is proposed based on the analysis.In a single-grounded mode of operation
the advantages and disadvantages
separate DC grounding electrode and common grounding with the converter station pole
is compared.Finally
in the event of single-phase ground fault occurs
the impact of equipment and personal safety is analyzed after increased ground potential
based on the calculation and analysis of sharing earth electrode
a reliable operation mode and grounding scheme is put forward.