LI Xiao, ZHANG Liang, WU Xiaogui, et al. Analysis of Waveform Parameters for Oscillating Lightning Impulse Voltage[J]. High voltageapparatus, 2018, 54(12): 238-244.
LI Xiao, ZHANG Liang, WU Xiaogui, et al. Analysis of Waveform Parameters for Oscillating Lightning Impulse Voltage[J]. High voltageapparatus, 2018, 54(12): 238-244. DOI: 10.13296/j.1001-1609.hva.2018.12.036.
Analysis of Waveform Parameters for Oscillating Lightning Impulse Voltage
To improve the reliability of gas insulated switchgear(GIS)
field impulse voltage withstand test is an important step.In recent years
oscillating lighting impulse voltage(OLI)has been commonly used in field test.Considering that OLI waveform varies with parameters of generator and load capacitance of GIS
we need to clarify the relationship between them theoretically.This paper establishes the third-order differential equation of output voltage based on the equivalent circuit.The time-domain expressions of OLI and its envelope are obtained.Waveform parameters are extracted
and the relationship between these waveform parameters and load capacitance
resistance
inductance are analyzed respectively.The results show that the oscillating frequency and front time are decided by inductance and capacitance of the circuit.The time to half-value are affected both by resistance and load capacitance.The generator efficiency decreases rapidly with the increase of the load capacitance.When the impulse voltage generator is designed with appropriate circuit parameters
even if the load capacitance varies in a wide range
the OLI waveform always meets the requirements of standard.The research achievements will provide good guide for waveform adjustment in field impulse voltage withstand test of GIS.