LU Jinfeng, ZHAO Qingchun, XIE Hua, et al. Scheme of Fault Phase Selection in Half-wavelength AC Transmission Line Based on Two-terminal Electrical Quantities[J]. High voltageapparatus, 2018, 54(12): 251-256.
LU Jinfeng, ZHAO Qingchun, XIE Hua, et al. Scheme of Fault Phase Selection in Half-wavelength AC Transmission Line Based on Two-terminal Electrical Quantities[J]. High voltageapparatus, 2018, 54(12): 251-256. DOI: 10.13296/j.1001-1609.hva.2018.12.038.
Scheme of Fault Phase Selection in Half-wavelength AC Transmission Line Based on Two-terminal Electrical Quantities
Half-wavelength AC transmission line(HWACT)is a high-voltage transmission line.So
it needs to correctly choose the fault phases after short circuit occurred in HWACT.Due to its unique electrical characteristics
the traditional phase selection element no longer applies.This paper proposes a scheme of fault phase selection in HWACT based on two-terminal electrical quantities.Two-terminal line voltage and two-terminal line current can be converted into positive and negative sequence of short circuit current
and then it can correctly choose the fault phases.The fault phase selection scheme is not affected by fault location
fault resistance and weak-infeed line.PSCAD simulation shows that the scheme can select the fault phase selection quickly and correctly.