WANG Meng, ZHANG Wenchao, GAO Xiangxiang, et al. Calculation of DC Component Characteristic Parameters of Power System Short-circuit Current Based on Integral and Difference Method[J]. High voltageapparatus, 2018, 54(12): 268-273+280.
WANG Meng, ZHANG Wenchao, GAO Xiangxiang, et al. Calculation of DC Component Characteristic Parameters of Power System Short-circuit Current Based on Integral and Difference Method[J]. High voltageapparatus, 2018, 54(12): 268-273+280. DOI: 10.13296/j.1001-1609.hva.2018.12.041.
Calculation of DC Component Characteristic Parameters of Power System Short-circuit Current Based on Integral and Difference Method
with the increase of DC time constant of power grid
which leads to DC component of short circuit decayed low and exceeded the interruption capability of circuit-breakers in the set time.Therefore
the calculation and evaluation of DC time constant is especially important for the optimal design and safe operation of power grid.In this paper
the integral method
difference method and combination method for calculating the characteristic parameters of DC component of short circuit current with three times and five times harmonic have been proposed.The results show that integral method
difference method and combination method can calculate the characteristic parameters of DC component with zero error for ideal short circuit current waveform.After superposing Gauss white noise signal the calculation precision of three algorithms is integral method
combination method and difference method in turn.What’s more
add the 60 dB Gaussian white noise calculation result is better than 30 dB Gaussian white noise.Furthermore
the DC component of short-circuit current measured in power system is calculated by integrating method
it is provided a new solution to calculated the characteristic parameters of DC component when varying to time.