Study on the Influence of Transformer Charging on UHVDC Operation in UHVAC and UHVDC Coupled Power Grid
With the increasing coupling degree of UHV AC/DC system and large-scale construction of UHV AC/DCproject
main transformer charging in multi-DC feed-in receiving end power grid has certain influence on the DCtransmission and the operation of the receiving end. According to the plan
in 2017 Suzhou station for important hubof Huaihu UHVAC southern half will be put into operation
in order to study the influence of charging on the opera-tion of Jinsu UHVDC during the commissioning of UHVAC Suzhou station
in the RTDS Jinsu UHVDC and HuaiHuUHVAC equivalent power grid is built
actual control and protection device are built to form a closed loop simulationplatform with RTDS. Its performance remains highly consistent with actual UHVDC project in protection functions
behavior under fault of AC and DC and other aspects of characteristics. The operation of JinSu UHVDC near-zonetransformer and UHVAC transformer after air-charging are simulated and analyzed. The results show
transformernear JinSu UHVDC charging will lead to cyclical commutation failure and blocking
but the Suzhou UHVAC trans-former empty charge has no significant effect on the UHVDC operation basically. The conclusion is of great reference significance for the commissioning of HuaiHu UHVAC project.