GIS Basin Insulator Defect Analysis Based on Ultra-high Frequency Time-frequency Analysis
For upgrading partial discharge on-site detect level of gas insulated switchgear(GIS)
detecting internaldefects of equipments quickly and exactly
especially partial discharge defect of basin insulator
this article re-searched on partial discharge synthetic location method for GIS based on ultra-high frequency time-frequency loca-tion analysis. Construction of multi-channel signals time delay location method and multi-channel time-frequencyanalysis method based on wavelet transform
according to the partial discharge ultra-high frequency signal time andfrequency variations
GIS partial discharge synthetic location can be achieved combination of equipment internalstructure and assembly process. In 220kV GIS on-site detection of one 500kV substation
this method located sur-face discharge of a basin insulator exactly. It has confirmed partial discharge synthetic location method for GIS basedon ultra-high frequency time-frequency location analysis can locate the GIS internal defects. The application can su-pervise equipment maintenance pertinently
shorten equipment maintenance time and improve equipment maintenance efficiency.