LAN Jian, FENG Ying, LI Xiangyang, et al. Experimental Comparative Study of the Temperature Rise Performance of Dry Air,N2 and SF6 Gas-insulated RMU[J]. High voltageapparatus, 2019, 55(1): 64-71.
LAN Jian, FENG Ying, LI Xiangyang, et al. Experimental Comparative Study of the Temperature Rise Performance of Dry Air,N2 and SF6 Gas-insulated RMU[J]. High voltageapparatus, 2019, 55(1): 64-71. DOI: 10.13296/j.1001-1609.hva.2019.01.011.
Experimental Comparative Study of the Temperature Rise Performance of Dry Air,N2 and SF6 Gas-insulated RMU
A series of study of the temperature rise performance comparison tests of gas-insulated RMU filling dryair
N
2
and SF
6
respectively under different gas pressures has been carried out. It has been found that the temperaturerise of RMU using dry air or N
2
as insulating medium is 5~12 K or 5~10 K higher than that of using SF
6
respectively
and highest points focus on solid insulation embedded component fixed connections and the temperature rise differ-ence value is nearly consistent under different gas pressures. If RMU filling the same insulat
ing gas under differentpressures
the temperature rise drops down by increasing of the gas pressure. The temperature rise of dry air or N
2
gas-insulated RMU has only 5% reduction within scopes of micro-positive pressures
which is not significant comparedwith SF
6
gas-insulated RMU. Research results provide references to guide the design