Feasibility Study on Installation Method of Surface Acoustic Wave(SAW)Sensor Circuit Breaker Contact Arm
Overheating of high voltage(HV)switchgear is a major source of asset failure and unplanned power outag-es. Most high voltage switchgears adopt metal clad structure
their electric connectors and conductors are shieldedby metal
and their temperatures are difficult to be measured by routine infrared temperature measurement device.Therefore
on-line temperature measurement systems are increasingly adopted to monitor the potential heating con-nectors of switchgear. Surface acoustic wave(SAW)on-line temperature measurement technology has many uniqueadvantages including passive and wireless design
high reliability
and lower maintenance. And SAW technologyhas become a widely adopted on-line temperature measurement technology. However
there are some divergences
even debates
about where to mount and how to mount these SAW sensors. Different installation locations and meth-ods can affect the safety of switchgear operation and the accuracy and effectiveness of SAW sensor’s monitoring data.This paper will illustrate the installation method of SAW sensor mounting on switchgear circuit breaker arms and dis-cuss the safety and effectiveness of this SAW installation method. The power frequency withstands voltage test
thelightning impulse test
and the partial discharge test are done to assess the insulation safety of the SAW installationmethod. Temperature-rise test is done to evaluate the accuracy
real-time
and effectiveness of the temperature monitoring data of SAW sensor mounting on switchgear circuit breaker arms.
Simulation and Experimental Study on Partial Discharge Decomposition Components of Air-insulated Switchgear Cabinet Considering the Influence of Temperature and Humidity
Fault Classification Method of Circuit Breaker Based on Improved Phase Trajectory Features of Coil Currents
Analysis on Oil Cylinder Cracking of Energy Storage Mechanism for 500 kV Circuit Breaker
Study on Electromagnetic Transient Characteristics During Switching Operation of 750 kV GIS Substation
Adjustment and Optimization Analysis Method of Opening Time for Circuit Breaker
Related Author
JI Hongquan
XIN Feng
LIU Ruoxi
WANG Zhihui
LUO Zhongge
GUI Yuan
CHEN Yaqi
FAN Ruixiang
Related Institution
Power Research Institute of State Grid Beijing Electric Power Co., Ltd.
State Grid Beijingg Electric Power Company
State Grid Beijing Electric Power Company Urban Power Supply Company
Institute of Electric Power Science, State Grid Jiangxi Electric Power Co., Ltd.
School of Information Engineering, Nanchang Hangkong University