YOU Zhixun, LIU Nan. Simulation Study on Ferroresonance and Its Suppression Measures in Hydropower Station[J]. High voltageapparatus, 2019, 55(1): 128-134.
YOU Zhixun, LIU Nan. Simulation Study on Ferroresonance and Its Suppression Measures in Hydropower Station[J]. High voltageapparatus, 2019, 55(1): 128-134. DOI: 10.13296/j.1001-1609.hva.2019.01.020.
Simulation Study on Ferroresonance and Its Suppression Measures in Hydropower Station
and threats the safety of the whole grid. Since the main rea-son of ferroresonance is nonlinear magnetic saturation of equipment with iron core
it is difficult to built accurate sim-ulation model. In this paper
PT is modeled with nonlinear reactor and ideal transformer
and the ferroresonance phe-nomena and its appearing conditions are accurately simulated. Based on the simulation
the suppression measure offerroresonance is proposed by using CVT. The simulation results show that utilizing CVT can effectively suppress theferroresonance in primary system. However
when short circuit happens at the secondary side of CVT and is eliminat-ed quickly
ferroresonance happens inside CVT. The reason of the internal ferroresonance is further analyzed
based on which the suppression measure of adding harmonic elimination resistance is proposed and verified.