Electromagnetic Effect on the Adjacent Gas Pipeline of the Lightning Strike on HV Transmission Lines
Using the case of 220kV double circuit transmission line on the same tower
a time domain simulation cal-culation model comprising the transmission line parameters
types of tower
insulator
gas pipeline and its protectivelayer is establishedby the electromagnetic transient simulation software ATP
which is used to analyze the effects oflightning location
mine current size
the horizontal spacing
the soil resistivity
the tower height and diameter of pipefor the interference of the gas transmission pipeline in the vicinity of the high voltage transmission line.The resultsshow that:AC interference of gas pipeline is strongly influenced by lightning point;AC interference is proportional tothe distance between pipeline and Tower Center
while the effects of the soil resistivity
pipeline diameter and thetower height are small. The conclusion provides theoretical guidance for the laying of gas pipeline in the vicinity of the high voltage line