LIU Mengjia, YU Yanzhu, YU Yiliang, et al. Broadband Detection and Analysis of Partial Discharge in Cross-connected Cables Based on Three-phase Amplitude-phase Relation Analysis[J]. High voltageapparatus, 2019, 55(1): 226-230+236.
LIU Mengjia, YU Yanzhu, YU Yiliang, et al. Broadband Detection and Analysis of Partial Discharge in Cross-connected Cables Based on Three-phase Amplitude-phase Relation Analysis[J]. High voltageapparatus, 2019, 55(1): 226-230+236. DOI: 10.13296/j.1001-1609.hva.2019.01.035.
Broadband Detection and Analysis of Partial Discharge in Cross-connected Cables Based on Three-phase Amplitude-phase Relation Analysis
The power cable is one of the most important transmission equipments. The long cable common use thecross bonded grounding method to reduce the loss of shielding layer and decerease the volatge rise at the end of ca-ble. Therefore
it is difficult to diagnosis the PD detection results of cross bonded cable in field because the PD sig-nals will be influence both the enviroment electromagnet interference and the interference among different phases.The broadband sensor is used to detect the PD of cross bonded cable in field in this paper. The waveforms of the PDpulse
PRPD and 3PARD diagrams are analyzed to diagnose the results. The results have shown that the broadbandsensor can anti the enviroment electromagnet interference because it can obtain more information of PD signal. The 3 PARD diagrams can division the interference among different phases.