Analysis and Treatment of GIS Defect Discovered by Live Detection of SF6 Decomposition Products
To investigate an abnormal of potential transformer(PT)in gas insulated switchgear(GIS)detected by livedetection of sulfur hexafluoride(SF
6
)decomposition products
the cause of failure is analyzed combining different de-composition products detection techniques
electric tests and equipment disassembling. The obtained results indi-cate that
the observed abnormal phenomenon is a without reported ultrahigh hydrogen content in SF
6
. The test re-sults from different electrochemical sensor instruments are quite different
and the data from c
hromatograph is moreaccurate. The main reason of PT defect is introducing some contaminants such as transformer oil from retired siliconsteel sheets. Meanwhile
under the longtime overheating from over-excitation of the defective iron core
evolution ofdissolved gas or decomposition of transformer oil and other materials result in the abnormal high of hydrogen in SF
6
.The defect of a PT is treated successfully by treatment suggestions. Some maintenance advices for similar equipmentare proposed. Furthermore
the modified ideas for decomposition products detection techniques and devices and use-ful technical guidance are proposed for security and stability of GIS equipment and power grid.