FEM Analysis on the Distribution of Internal Radial Potential Along ±800 kV DC Voltage Divider
As the different electrical potential between internal resistance-capacitance unit and outdoor insulation
the radial potential difference between resistance-capacitance unit and Hollow insulator is inevitable.In order to find out the relationship between the internal radial potential of DC voltage divider and the surrounding environment
a FEM(Finite Element Method)analysis are carried out by the example of ±800 kV DC voltage divider with composite housing.The internal radial potential of DC voltage divider under the dry condition
uniform wet pollution
non-uniform wet pollution and heavy rain conditions are calculated.The simulation results show that the maximum radial potential of the DC divider subjected to dry condition is about 60 kV located at the second resistance-capacitance unit near the high voltage terminal.For the case of wet and polluted condition
the radial potential is about3 kV larger than that in the case of dry condition.When heavy rain and part of the sheds of the composite housing are bridged by the rain
the maximum radial potential increases
and the displacement is related to the length and location of the sheds bridged.With the increase of internal radial potential
the voltage divider will run the high risk of radial discharge.Thus then the radial potential under different environment conditions are strongly recommended to consider in the insulation design of DC voltage divider.