In order to verify the VFTO suppression effect of the restraining busbar
the VFTO suppression verification test was carried out on a 550 kV GIS test platform.In order to carry out the test
the dimensions of the test platform were optimized according to the IEC 62271-102—2013 standard.According to the working conditions of GIS
the test conditions of AC
DC
disconnector opening and closing are designed.From the aspect of VFTO
the duration
the number of breakdowns and the frequency components
the test results before and after the installation of the restraining busbar are summarized and analyzed.The test results show that the maximum amplitude of VFTO can be reduced from 2.42 p.u.to 1.49 p.u.before installation;the amplitude suppression ratio can reach up to 52.94%
and the minimum is also 22.22%;after installing the restraining busbar
the number of full-wave breakdown can be reduced from 13 times to 5 times
the duration is reduced from 7 power frequency cycles to 2.5 power frequency cycles;at the same time
the test results reveale that the restraining busbar has a significant effect on the high frequency component suppression of VFTO.The verification test shows that the restraining busbar has a good suppression effect on VFTO