Simulated Experimental Study on Transient Electric Field of 110 kV AIS Disconnector During Opening and Closing Operation
in order to study the influence of the space electromagnetic environment generated by the disconnector operated on the no-load bus to the electronic transformer
a large number of repeated tests are required to obtain the spatial electromagnetic environment change rule.However
a large number of repeated tests in substations are forbidden.Therefore
this paper designs a simulated disturbance source system that can simulate the actual disconnector operation.The system can be used to study the law of the electric field generated by 110 k V AIS disconnector’s operation with different parameters.The experimental results show that the system can generate spatial transient electric field with frequency of 0.9 MHz to 2 MHz and intensity of 6 kV to 20 kV
which is in good agreement with the measured electric field data of the 110 kV AIS station reported in the existing literature.